1
GATE EE 2024
Numerical
+1
-0

The incremental cost curves of two generators (Gen A and Gen B) in a plant supplying a common load are shown in the figure. If the incremental cost of supplying the common load is Rs. 7400 per MWh, then the common load in MW is ________ (rounded off to the nearest integer).

GATE EE 2024 Power System Analysis - Power Generation Cost Question 4 English
Your input ____
2
GATE EE 2022
Numerical
+1
-0
If only 5% of the supplied power to a cable reaches the output terminal, the power loss in the cable, in decibels, is ______. (round off to nearest integer).
Your input ____
3
GATE EE 2021
MCQ (Single Correct Answer)
+1
-0.33

Two generators have cost functions $F_1$ and $F_2$. Their incremental-cost characteristics are

$$ \frac{d F_1}{d P_1}=40+0.2 P_1 \text { and } \frac{d F_2}{d P_2}=32+0.4 P_2 $$

They need to deliver a combined load of 260 MW . Ignoring the network losses, for economic operation, the generations $P_1$ and $P_2$ (in MW) are

A

$P_1=P_2=130$

B

$P_1=160, P_2=100$

C

$P_1=140, P_2=120$

D

$P_1=120, P_2=140$

4
GATE EE 2012
MCQ (Single Correct Answer)
+1
-0.3
The figure shows a two-generator system supplying a load of $${P_D} = 40\,MW,$$ connected at bus $$2.$$ GATE EE 2012 Power System Analysis - Power Generation Cost Question 19 English

The fuel cost of generators $${G_1}$$ and $${G_2}$$ are: $${C_1}\left( {{P_{G1}}} \right) = 10,000\,\,Rs/MWhr$$ and $${C_2}\left( {{P_{G2}}} \right) = 12,500\,\,Rs/MWhr$$ and the loss in the line is $$\,{P_{loss(pu)}} = 0.5\,\,P_{G1\left( {pu} \right),}^2\,\,\,\,$$ where the loss coefficient is specified in pu on a $$100$$ $$MVA$$ base. The most economic power generation schedule in $$MW$$ is

A
$${P_{G1}} = 20,\,{P_{G2}} = 22$$
B
$${P_{G1}} = 22,\,{P_{G2}} = 20$$
C
$${P_{G1}} = 20,\,{P_{G2}} = 22$$
D
$${P_{G1}} = 0,\,{P_{G2}} = 40$$

GATE EE Subjects