Switch Gear and Protection · Power System Analysis · GATE EE

Start Practice

Marks 1

1

For the three-bus power system shown in the figure, the trip signals to the circuit breakers B$$_1$$ to B$$_9$$ are provided by overcurrent relays R$$_1$$ to R$$_9$$, respectively, some of which have directional properties also. The necessary condition for the system to be protected for short circuit fault at any part of the system between bus 1 and the R-L loads with isolation of minimum portion of the network using minimum number of directional relays is

GATE EE 2023 Power System Analysis - Switch Gear and Protection Question 1 English

GATE EE 2023
2

The most commonly used relay, for the protection of an alternator against loss of excitation, is

GATE EE 2022
3
A negative sequence relay is commonly used to protect
GATE EE 2011
4
A two machine power system in shown below. Transmission line $$XY$$ has positive sequence impedance of $${Z_1}\Omega $$ and zero sequence impedance of $${Z_0}\Omega $$ GATE EE 2008 Power System Analysis - Switch Gear and Protection Question 16 English
An $$'a'$$ phase to ground fault with zero fault impedance occurs at the centre of the transmission line. Bus voltage at $$X$$ and line current from $$X$$ to $$F$$ for the phase $$'a',$$ are given by $${V_a}$$ Volts and $${{\rm I}_a}$$ Amperes, respectively. Then, the impedance measured by the ground distance relay located at the terminal $$X$$ of line $$XY$$ will be given by
GATE EE 2008
5
In a biased differential relay the bias is defined as a ratio of
GATE EE 2006
6
The transmission line distance protection relay having the property of being inherently directional is
GATE EE 2004
7
Consider the problem of relay co-ordination for the distance relays $$R1$$ and $$R2$$ on adjacent lines of a transmission system figure. The Zone $$1$$ GATE EE 2002 Power System Analysis - Switch Gear and Protection Question 19 English
and Zone $$2$$ settings for both the relays are indicated on the diagram. Which of the following indicates the correct time setting for the Zone $$2$$ of relays $$R1$$ and $$R2.$$
GATE EE 2002
8
In an inverse definite minimum time, electromagnetic type over-current relay, the minimum time feature is achieved because of
GATE EE 2000
9
In a 3-step distance protection, the reach of the three zones of the relay at the beginning of the first line typically extends upto
GATE EE 2000
10
Reactance relay is normally preferred for protection against
GATE EE 1997
11
If the fault current is $$2000$$ A, the relay setting is $$50$$% and CT ratio is $$400:5,$$ the plug setting multiplier will be
GATE EE 1996
12
A Buchholz relay is used for
GATE EE 1992

Marks 2

1
A $$3$$-phase transformer rated for $$33 kV/11kV$$ is connected in delta/star as shown in figure. The current transformers $$\left( {C{T_s}} \right)$$ on low and high voltage sides have a ratio of $$500/5.$$ Find the currents $${i_1}$$ and $${i_2}$$, if the fault current is $$300$$ $$A$$ as shown in figure. GATE EE 2015 Set 2 Power System Analysis - Switch Gear and Protection Question 6 English
GATE EE 2015 Set 2
2
The over current relays for the line protection and loads connected at the buses are shown in the figure. GATE EE 2014 Set 1 Power System Analysis - Switch Gear and Protection Question 7 English

The relays are IDMT is natural having the characteristic
$${t_{op}} = {{0.14\, \times \,time\,\,multiplier\,\,setting} \over {{{(plug\,\,setting\,\,multiplier)}^{0.02}} - 1}}$$
The maximum and minimum fault current at bus $$B$$ are $$2000A$$ and $$500$$ $$A$$ respectively. Assuming the time multiplier setting and plug setting for relay $${R_B}$$ to be $$0.1$$ and $$5$$ $$A$$ respectively, the operating time of $${R_B}$$ (in seconds) is __________.

GATE EE 2014 Set 1
3
Consider a stator winding of an alternator with an internal high resistance ground fault. The currents under the fault condition are as shown in the figure. The winding is protected using a differential current scheme with current transformers of ratio $$400/5$$ $$A$$ as shown. The current through the operating coil is GATE EE 2010 Power System Analysis - Switch Gear and Protection Question 8 English
GATE EE 2010
4
Match the items in List-$$I$$ (Type of transmission line) with the items in List-$$II$$ (Type of distance relay preferred) and select the correct answer using the codes below the lists.

List-$$I$$
$$A.$$ Short Line
$$B.$$ Mesium Line
$$C.$$ Long Line

List-$$II$$
$$1.$$ Ohm Relay
$$2.$$ Reactance Relay
$$3.$$ Mho Relay

GATE EE 2009
5
Voltage phasors at the two terminals of a transmission line of length $$70$$ km have a magnitude of $$1.0$$ per unit but are $$180$$ degrees out of phase. Assuming that the maximum load current in the line is $$1/5$$th of minimum $$3$$-phase fault current. Which one of the following transmission line protection schemes will NOT pick up for this condition?
GATE EE 2008
6
A list of relays and the power system components protected by the relays are given in List-$${\rm I}$$ and List-$${\rm II}$$ respectively. Choose the correct match from the four choices given below

List-$${\rm I}$$
$$A.$$ Distance relay
$$B.$$ Under frequency relay
$$C.$$ Differential relay
$$D.$$ Buchholz relay

List-$${\rm II}$$
$$1.$$ Transformers
$$2.$$ Turbines
$$3.$$ Busbars
$$4.$$ Shunt capacitors
$$5.$$ Alternators
$$6.$$ Transmission lines

GATE EE 2003
7
The plug setting of a negative sequence relay is $$0.2$$ $$A.$$ The current transformer ratio is $$5:1$$. The minimum value of line to line fault current for the operation of the relay is
GATE EE 2000
8
The neutral of $$10$$ $$MVA,$$ $$11$$ $$kV$$ alternator is earthed through a resistance of $$5$$ ohms. The earth fault relay is set to operate at $$0.75$$ $$A.$$ The $$CT's$$ have a ratio of $$1000/5.$$ What percentage of the alternator winding is protected?
GATE EE 1998
9
The distribution system shown in figure is to be protected by over current system of protection. For proper fault discrimination directional over current relays will be required at locations GATE EE 1993 Power System Analysis - Switch Gear and Protection Question 14 English
GATE EE 1993

Marks 5

EXAM MAP
Medical
NEETAIIMS
Graduate Aptitude Test in Engineering
GATE CSEGATE ECEGATE EEGATE MEGATE CEGATE PIGATE IN
Civil Services
UPSC Civil Service
Defence
NDA
Staff Selection Commission
SSC CGL Tier I
CBSE
Class 12