Switch Gear and Protection · Power System Analysis · GATE EE
Marks 1
For the three-bus power system shown in the figure, the trip signals to the circuit breakers B$$_1$$ to B$$_9$$ are provided by overcurrent relays R$$_1$$ to R$$_9$$, respectively, some of which have directional properties also. The necessary condition for the system to be protected for short circuit fault at any part of the system between bus 1 and the R-L loads with isolation of minimum portion of the network using minimum number of directional relays is
The most commonly used relay, for the protection of an alternator against loss of excitation, is
An $$'a'$$ phase to ground fault with zero fault impedance occurs at the centre of the transmission line. Bus voltage at $$X$$ and line current from $$X$$ to $$F$$ for the phase $$'a',$$ are given by $${V_a}$$ Volts and $${{\rm I}_a}$$ Amperes, respectively. Then, the impedance measured by the ground distance relay located at the terminal $$X$$ of line $$XY$$ will be given by

and Zone $$2$$ settings for both the relays are indicated on the diagram. Which of the following indicates the correct time setting for the Zone $$2$$ of relays $$R1$$ and $$R2.$$
Marks 2


The relays are IDMT is natural having the characteristic
$${t_{op}} = {{0.14\, \times \,time\,\,multiplier\,\,setting} \over {{{(plug\,\,setting\,\,multiplier)}^{0.02}} - 1}}$$
The maximum and minimum fault current at bus $$B$$ are $$2000A$$ and $$500$$ $$A$$ respectively. Assuming the time multiplier setting and plug setting for relay $${R_B}$$ to be $$0.1$$ and $$5$$ $$A$$ respectively, the operating time of $${R_B}$$ (in seconds) is __________.

List-$$I$$
$$A.$$ Short Line
$$B.$$ Mesium Line
$$C.$$ Long Line
List-$$II$$
$$1.$$ Ohm Relay
$$2.$$ Reactance Relay
$$3.$$ Mho Relay
List-$${\rm I}$$
$$A.$$ Distance relay
$$B.$$ Under frequency relay
$$C.$$ Differential relay
$$D.$$ Buchholz relay
$$1.$$ Transformers
$$2.$$ Turbines
$$3.$$ Busbars
$$4.$$ Shunt capacitors
$$5.$$ Alternators
$$6.$$ Transmission lines

Marks 5
Type of Relay
$$A.$$ Buchholz Relay
$$B.$$ Translay relay
$$C.$$ Carrier current, phase comparison relay
$$D.$$ Directional over Current relay
$$E.$$ Negative sequence relay
Most suited for
$$P.$$ Feeder
$$Q.$$ Transformer
$$R.$$ Radial distributed
$$S.$$ Generator
$$T.$$ Ring main distributor
$$U.$$ Long over head transmission line