1
GATE EE 2003
MCQ (Single Correct Answer)
+2
-0.6
A surge of 20 kV magnitude travels along a lossless cable towards its junction with two identical lossless overhead transmission lines. The inductance and the capacitance of the cable are 0.4 mH and 0.5 $$\mu F$$ per km. The inductance and capacitance of the overhead transmission lines are 1.5 mH and 0.015 $$\mu F$$ per km. The magnitude of the voltage at the junction due to surge is
A
36.72 kV
B
18.36 kV
C
6.07 kV
D
33.93 kV
2
GATE EE 2003
MCQ (Single Correct Answer)
+2
-0.6
The ABCD parameters of a $$3$$-phase overhead transmission line are $$\,A = D = 0.9\angle {0^ \circ }.\,\,B = 200\,\angle {90^ \circ }\,\,\Omega \,\,\,$$ and $$\,\,C = 0.95\, \times \,\,{10^{ - 3}}\angle {90^ \circ }\,\,S.\,\,\,\,$$ At no-load condition, a shunt inductive reactor is connected at the receiving end of the line to limit the receiving end voltage to be equal to the sending-end voltage. The ohmic value of the reactor is
A
$$\infty \Omega $$
B
$$2000\,\Omega $$
C
$$105.26\,\Omega $$
D
$$1052.6\,\Omega $$
3
GATE EE 2003
MCQ (Single Correct Answer)
+1
-0.3
Bundled conductors are mainly used in high voltage overhead transmission lines to
A
Reduce transmission line losses
B
Increase mechanical strength of the line
C
Reduce corona
D
Reduce sag
4
GATE EE 2003
MCQ (Single Correct Answer)
+1
-0.3
A $$3$$-phase, $$11$$-$$kV$$ generator feeds power to a constant power unity power factor load of $$100$$ $$MW$$ through a $$3$$-phase transmission line. The line-to-line voltage at the terminals of the machine is maintained constant at $$11$$ $$kV$$. The per unit positive sequence impedance of the line based on $$100$$ $$MVA$$ and $$11$$ $$kV$$ is $$j$$ $$0.2$$. The line to line voltage at the load terminals is measured to be less than $$11$$ $$kV$$. The total reactive power to be injected at the terminals of the load to increase the line-to-line voltage at the load terminals to $$11$$ $$kV$$ is
A
$$100$$ MVAR
B
$$10.1$$ MVAR
C
$$-100$$ MVAR
D
$$-10.1$$ MVAR