1
GATE EE 2002
Subjective
+5
-0
A $$415$$ $$V,$$ $$2$$ pole, $$3$$ phase, $$50$$ $$Hz,$$ star connected, non-salient pole synchronous motor has synchronous reactance of $$2\,\Omega $$ per phase and negligible stator resistance. At a particular field excitation, it draws 20 A at unity power factor from a $$415$$ $$V,$$ $$3$$ phase, $$50$$ $$Hz$$ supply. The mechanical load on the motor is now increased till the stator current is equal to $$50$$ $$A.$$ The field excitation remains unchanged. Determine:
$$(a)$$ the per phase open circuit voltage $${E_0}$$
$$(b)$$ the developed power for the new operating condition and corresponding power factor.
2
GATE EE 2002
MCQ (Single Correct Answer)
+2
-0.6
The flux per pole in a synchronous motor with the field circuit ON and the stator disconnected from the supply is found to be $$25$$ $$mWb.$$ When the stator is connected to the rated supply with the field excitation unchanged, the flux per pole in the achine is found to be $$20$$ $$mWb$$ while the motor is running on no load. Assuming no load losses to be zero, the no load current down by the motor from the supply
A
lags the supply voltage
B
leads the supply voltage
C
is in phase with the supply voltage
D
is zero
3
GATE EE 2002
Subjective
+5
-0
A single phase $$6300$$ $$kVA,$$ $$50$$ $$Hz,$$ $$3300V/400V$$ distribution transformer is connected between two $$50$$ $$Hz$$ supply systems, $$A$$ and $$B$$ as shown in Fig. The transformer has $$12$$ and $$99$$ turns in the low and high voltage windings respectively. The magnetizing reactance of the transformer referred to the high voltage side is $$500\Omega .$$ The leakage reactance of the high and low voltage windings are $$1.0\Omega $$ and $$0.012\Omega $$ respectively. Neglect the winding resistance and core losses of the transformer. The Thevenin voltage of system $$A$$ is $$3300V$$ while that of system $$B$$ is $$400V.$$ the short circuit reactance of systems $$A$$ and $$B$$ are $$0.5\Omega $$ and $$0.010\Omega $$ respectively. If no power is transferred between $$A$$ and $$B,$$ so that the two system voltages are in phase, find the magnetizing ampere turns of the transformer. GATE EE 2002 Electrical Machines - Transformers Question 10 English
4
GATE EE 2002
Subjective
+5
-0
In a single phase $$3$$ winding transformer the turns ratio for primary: secondary: tertiary windings is $$20:4:1.$$ With the lagging currents of $$50A$$ at a power factor of $$0.6$$ in the tertiary winding find the primary current and power factor.
EXAM MAP
Medical
NEETAIIMS
Graduate Aptitude Test in Engineering
GATE CSEGATE ECEGATE EEGATE MEGATE CEGATE PIGATE IN
Civil Services
UPSC Civil Service
Defence
NDA
Staff Selection Commission
SSC CGL Tier I
CBSE
Class 12