1
GATE EE 2008
MCQ (Single Correct Answer)
+2
-0.6
Given that: $$\,{V_{s1}} = {V_{s2}} = 1 + j0\,\,p.u,\,\, + ve\,\,$$ sequence impedance are $$\,{Z_{s1}} = {Z_{s2}} = 0.001 + j0.01\,\,p.u\,\,$$ and $${Z_L} = 0.006 + j\,0.06\,\,p.u,\,\,3\phi .\,\,\,$$ Base $$MVA=100,$$ voltage base $$=400$$ $$kV(L-L).$$
Nominal system frequency $$= 50$$ $$Hz.$$ The reference voltage for phase $$'a'$$ is defined as $$\,\,V\left( t \right) = {V_m}\,\cos \left( {\omega t} \right).\,\,\,$$ A symmetrical $$3\phi $$ fault occurs at centre of the line, i.e., at point $$'F'$$ at time 'to' the $$+ve$$ sequence impedance from source $${S_1}$$ to point $$'F'$$ equals $$(0.004 + j \,\,0.04)$$ $$p.u.$$ The wave form corresponding to phase $$'a'$$ fault current from bus $$X$$ reveals that decaying $$d.c.$$ offset current is $$-ve$$ and in magnitude at its maximum initial value. Assume that the negative sequence are equal to $$+ve$$ sequence impedances and the zero sequence $$(Z)$$ are $$3$$ times $$+ve$$ sequence $$(Z).$$

The $$rms$$ value of the ac component of fault current $$\,\left( {{{\rm I}_x}} \right)$$ will be

A
$$3.59$$ $$kA$$
B
$$5.07$$ $$kA$$
C
$$7.18$$ $$kA$$
D
$$10.15$$$$kA$$
2
GATE EE 2008
MCQ (Single Correct Answer)
+1
-0.3
A two machine power system in shown below. Transmission line $$XY$$ has positive sequence impedance of $${Z_1}\Omega $$ and zero sequence impedance of $${Z_0}\Omega $$ GATE EE 2008 Power System Analysis - Switch Gear and Protection Question 17 English
An $$'a'$$ phase to ground fault with zero fault impedance occurs at the centre of the transmission line. Bus voltage at $$X$$ and line current from $$X$$ to $$F$$ for the phase $$'a',$$ are given by $${V_a}$$ Volts and $${{\rm I}_a}$$ Amperes, respectively. Then, the impedance measured by the ground distance relay located at the terminal $$X$$ of line $$XY$$ will be given by
A
$${Z_1}/2\Omega $$
B
$${Z_0}/2\Omega $$
C
$$\left( {{Z_0} + {Z_1}} \right)/2\Omega $$
D
$${V_a}/{{\rm I}_a}\,\Omega $$
3
GATE EE 2008
MCQ (Single Correct Answer)
+1
-0.3
A 3-phase transmission line is shown in figure: GATE EE 2008 Power System Analysis - Symmetrical Components and Symmetrical and Unsymmetrical Faults Question 43 English

Voltage drop across the transmission line is given by the following equation: $$$\left[ {\matrix{ {\Delta {V_a}} \cr {\Delta {V_b}} \cr {\Delta {V_c}} \cr } } \right] = \left[ {\matrix{ {{Z_s}} & {{Z_m}} & {{Z_m}} \cr {{Z_m}} & {{Z_s}} & {{Z_m}} \cr {{Z_m}} & {{Z_m}} & {{Z_s}} \cr } } \right]\left[ {\matrix{ {{i_a}} \cr {{i_b}} \cr {{i_c}} \cr } } \right]$$$
Shunt capacitance of the line can be neglect. If the line has positive sequence impedance of $$15\,\,\Omega $$ and zero sequence in impedance of $$48\,\,\Omega ,$$ then the values of $${{Z_s}}$$ and $${{Z_m}}$$ will be

A
$${Z_s} = 31.5\,\Omega ;\,\,{Z_m} = 16.5\,\Omega $$
B
$${Z_s} = 26\,\Omega ;\,\,{Z_m} = 11\,\Omega $$
C
$${Z_s} = 16.5\,\Omega ;\,\,{Z_m} = 31.5\,\Omega $$
D
$${Z_s} = 11\,\Omega ;\,\,{Z_m} = 26\,\Omega $$
4
GATE EE 2008
MCQ (Single Correct Answer)
+1
-0.3
An extra high voltage transmission line of length $$300$$ km can be approximate by a lossless line having propagation constant $$\beta = 0.00127$$ radians per km. then the percentage ratio of line length to wavelength will be given by
A
$$24.24$$%
B
$$12.12$$%
C
$$19.05$$%
D
$$6.06$$%