1
GATE EE 2008
MCQ (Single Correct Answer)
+2
-0.6
A lossless transmission line having Surge Impedance Loading $$(SIL)$$ of $$2280$$ $$MW.$$ A Series capacitive compensation of $$30$$% is emplaced. Then $$SIL$$ of the compensated transmission line will be
A
$$1835$$ $$MW$$
B
$$2280$$ $$MW$$
C
$$2725$$ $$MW$$
D
$$3257$$ $$MW$$
2
GATE EE 2008
MCQ (Single Correct Answer)
+1
-0.3
An extra high voltage transmission line of length $$300$$ km can be approximate by a lossless line having propagation constant $$\beta = 0.00127$$ radians per km. then the percentage ratio of line length to wavelength will be given by
A
$$24.24$$%
B
$$12.12$$%
C
$$19.05$$%
D
$$6.06$$%
3
GATE EE 2008
MCQ (Single Correct Answer)
+1
-0.3
A two machine power system in shown below. Transmission line $$XY$$ has positive sequence impedance of $${Z_1}\Omega $$ and zero sequence impedance of $${Z_0}\Omega $$ GATE EE 2008 Power System Analysis - Switch Gear and Protection Question 16 English
An $$'a'$$ phase to ground fault with zero fault impedance occurs at the centre of the transmission line. Bus voltage at $$X$$ and line current from $$X$$ to $$F$$ for the phase $$'a',$$ are given by $${V_a}$$ Volts and $${{\rm I}_a}$$ Amperes, respectively. Then, the impedance measured by the ground distance relay located at the terminal $$X$$ of line $$XY$$ will be given by
A
$${Z_1}/2\Omega $$
B
$${Z_0}/2\Omega $$
C
$$\left( {{Z_0} + {Z_1}} \right)/2\Omega $$
D
$${V_a}/{{\rm I}_a}\,\Omega $$
4
GATE EE 2008
MCQ (Single Correct Answer)
+2
-0.6
Voltage phasors at the two terminals of a transmission line of length $$70$$ km have a magnitude of $$1.0$$ per unit but are $$180$$ degrees out of phase. Assuming that the maximum load current in the line is $$1/5$$th of minimum $$3$$-phase fault current. Which one of the following transmission line protection schemes will NOT pick up for this condition?
A
Distance protection using mho relays with zone-$$1$$ set to $$80$$% of the line impedance.
B
Directional over current protection set to pick up at $$1.25$$ times the maximum load current
C
Pilot relaying system with directional comparison scheme
D
Pilot relaying system with segregated phase comparison scheme.
EXAM MAP
Medical
NEETAIIMS
Graduate Aptitude Test in Engineering
GATE CSEGATE ECEGATE EEGATE MEGATE CEGATE PIGATE IN
Civil Services
UPSC Civil Service
Defence
NDA
Staff Selection Commission
SSC CGL Tier I
CBSE
Class 12