1
GATE EE 2007
MCQ (Single Correct Answer)
+1
-0.3
A single $$-$$ phase fully controlled thyristor bridge $$ac$$ $$-$$ $$dc$$ converter is operating at a firing angle of $${25^ \circ }$$ and an overlap angle of $${10^ \circ }$$ constant $$dc$$ output current of $$20$$ $$A$$. The fundamental power factor (displacement factor) at input $$ac$$ mains is
A
$$0.78$$
B
$$0.827$$
C
$$0.866$$
D
$$0.9$$
2
GATE EE 2007
MCQ (Single Correct Answer)
+2
-0.6
$$230$$ $$V$$ (phase) $$50$$ Hz, three-phase, $$4$$-wire, system has a sequence $$ABC$$. A unity power-factor load of $$4$$ kW is connected between phase A and neutral $$N$$. It is desired to achieve zero neutral current through the use of a pure inductor and pure capacitor in the other two phases. The Value of inductor and capacitor is......
A
$$72.95$$ $$mH$$ in phase $$C$$ & $$139.02$$ $$\mu F$$ in Phase $$B$$
B
$$72.95$$ $$mH$$ in Phase $$B$$ & $$139.02$$ $$\mu F$$ in Phase $$C$$
C
$$42.12$$ $$mH$$ in Phase $$C$$ & $$240.79$$ $$\mu F$$ in Phase $$B$$
D
$$42.12$$ $$mH$$ in Phase $$B$$ & $$240.79$$ $$\mu F$$ in Phase $$C$$
3
GATE EE 2007
MCQ (Single Correct Answer)
+1
-0.3
Two regional system, each having several synchronous generators and loads are interconnected by an ac line and a HVDC link as shown in the figure. Which of the following statements is true in the steady state: GATE EE 2007 Power System Analysis - High Voltage Dc Transmission Question 3 English
A
Both regions need not have the same frequency
B
The total power flow between the regions (Pac + Pdc) can be changed by controlling the HVDC converters alone
C
The power sharing between the ac line and the HVDC link can be changed by controlling the HVDC converters alone.
D
The directions of power flow in the HVDC link (Pdc) cannot be reversed.
4
GATE EE 2007
MCQ (Single Correct Answer)
+2
-0.6
Consider the protection system shown in the figure below. The circuit breakers numbered from $$1$$ to $$7$$ are of identical type. A single line to ground fault with zero fault impedance occurs at the midpoint of the line (at point F), but circuit breaker $$4$$ fails to operate (''Stuck breaker''). If the relays are coordinated correctly, a valid sequence of circuit breaker operation is GATE EE 2007 Power System Analysis - Circuit Breaker Question 3 English b
A
$$1,2,6,7,3,5$$
B
$$1,2,5,5,7,3$$
C
$$5,6,7,3,1,2$$
D
$$5,1,2,3,6,7$$