GATE EE 2017 Set 1
MCQ (Single Correct Answer)
+1
-0.3
A source is supplying a load through a 2-phase, 3-wire transmission system as shown in figure below. The instantaneous voltage and current in phase-a are $$v_{an}=220\sin\left(100\mathrm{πt}\right)\;V$$ and $$i_a=10\sin\left(100\mathrm{πt}\right)\;A$$, respectively. Similarly for phase-b the instantaneous voltage and current are $$v_{bn}=220\cos\left(100\mathrm{πt}\right)\;V$$ and $$i_b=10\cos\left(100\mathrm{πt}\right)\;A$$, respectively. GATE EE 2017 Set 1 Power System Analysis - Parameters and Performance of Transmission Lines Question 96 English The total instantaneous power flowing form the source to the load is
A
2200 W
B
$$2200\;\sin^2\left(100\mathrm{πt}\right)\;W$$
C
4400 W
D
$$2200\;\sin\left(100\mathrm{πt}\right)\cos\left(100\mathrm{πt}\right)\;W$$
2
GATE EE 2017 Set 1
MCQ (Single Correct Answer)
+2
-0.6
A load is supplied by a $$230$$ $$V,$$ $$50$$ $$Hz$$ source. The active power $$P$$ and the reactive power $$Q$$ consumed by the load are such that $$1$$ $$kW$$ $$ \le P \le 2\,kW\,\,$$ and $$\,1\,\,kVAR \le 2\,\,kVAR.\,\,$$ A capacitor connected across the load for power factor correction generates $$1$$ $$kVAR$$ reactive power. The worst case power factor after power factor correction is
A
$$0.447$$ lag
B
$$0.707$$ lag
C
$$0.894$$ lag
D
$$1$$
3
GATE EE 2017 Set 1
Numerical
+2
-0
The figure shows the single line diagram of a power system with a double circuit transmission line. The expression for electrical power is $$\,1.5\,\,\sin \delta ,\,\,$$ where $$\delta $$ is the rotor angle. The system is operating at the stable equilibrium point with mechanical power equal to $$1$$ pu. If one of the transmission line circuits is removed, the maximum value of $$\delta ,$$ as the rotor swings is $$1.221$$ radian. If the expression for electrical power with one transmission line circuit removed is $$\,{P_{\max }}\,\sin \delta ,\,\,$$ the valueof $${P_{\max }}\,,$$ in pu is _________. GATE EE 2017 Set 1 Power System Analysis - Power System Stability Question 12 English
Your input ____
4
GATE EE 2017 Set 1
Numerical
+2
-0
The positive, negative and zero sequence reactances of a wye-connected synchronous generator are 0.2 pu, 0.2 pu, and 0.1 pu, respectively. The generator is on open circuit with a terminal voltage of 1 pu. The minimum value of the inductive reactance, in pu, required to be connected between neutral and ground so that the fault current does not exceed 3.75 pu if a single line to ground fault occurs at the terminals is _______ (assume fault impedance to be zero). (Give the answer up to one decimal place)
Your input ____