1
GATE EE 2006
MCQ (Single Correct Answer)
+2
-0.6
An $$SCR$$ having a turn ON time of $$5\,\,\mu \,\,\sec $$, latching current of $$50$$ $$mA$$ and holding current of $$40$$ $$mA$$ is triggered by a short duration pulse and is used in the circuit shown in figure The minimum pulse width required To turn the $$SCR$$ ON will be GATE EE 2006 Power Electronics - Power Semiconductor Devices Question 7 English
A
$$251\,\,\mu \,\,\sec $$
B
$$150\,\,\mu \,\,\sec $$
C
$$100\,\,\mu \,\,\sec $$
D
$$5\,\,\mu \,\,\sec $$
2
GATE EE 2006
MCQ (Single Correct Answer)
+2
-0.6
A solar cell of $$350V$$ is feeding power to an $$ac$$ supply of $$440$$ $$V,$$ $$50$$ $$Hz$$ through a $$3$$- phase fully controlled briodge converter. A large inductance is connected in the $$dc$$ circuit to maintain the $$dc$$ current at $$20A.$$ If the solar cell resistance of $$0.5\Omega ,$$ then each thryristor will be reverse biased for a period of
A
$${125^ \circ }$$
B
$${120^ \circ }$$
C
$${60^ \circ }$$
D
$${55^ \circ }$$
3
GATE EE 2006
MCQ (Single Correct Answer)
+2
-0.6
A $$3$$ $$-$$ phase fully controlled bridge converter with free wheeling diode is fed from $$400$$ $$V$$, $$50$$ $$Hz$$ $$AC$$ source and is operating at a firing angle of $${60^ \circ }.$$ The load current is assumed constant at $$10A$$ due to high load inductance The input displacement factor $$(IDF)$$ and the input power factor $$(IPF)$$ of the converter will be
A
$$IDF=0.867:IPF=0.828$$
B
$$IDF=0.867:IPF=0.552$$
C
$$IDF=0.5:IPF=0.478$$
D
$$IDF=0.5:IPF=0.318$$
4
GATE EE 2006
MCQ (Single Correct Answer)
+2
-0.6
For a power system the admittance and impedance matrices for the fault studies are as follows. $$$\eqalign{ & {Y_{bus}} = \left[ {\matrix{ { - j8.75} & {j1.25} & {j2.50} \cr {j1.25} & { - j6.25} & {j2.50} \cr {j2.50} & {j2.50} & { - j5.00} \cr } } \right] \cr & {Z_{bus}} = \left[ {\matrix{ {j0.16} & {j0.08} & {j0.12} \cr {j0.08} & {j0.24} & {j0.16} \cr {j0.12} & {j0.16} & {j0.34} \cr } } \right] \cr} $$$

The pre-fault voltages are $$1.0$$ $$p.u.$$ at all the buses. The system was unloaded prior to the fault. A solid $$3$$ phase fault takes place at bus $$2.$$

The per unit fault feeds from generators connected to buses $$1$$ and $$2$$ respectively are

A
$$1.20, 2.51$$
B
$$1.55, 2.61$$
C
$$1.66, 2.50$$
D
$$5.00,2.50$$