1
GATE EE 2006
MCQ (Single Correct Answer)
+2
-0.6
Two transformers are to be operated in parallel such that they share load in proportion to their $$kVA$$ ratings. The rating of the first transformer is $$500$$ $$kVA$$ and its $$pu$$ leakage impedance is $$0.05$$ $$pu.$$ If the rating of second transformer is $$250$$ $$kVA,$$ its $$pu$$ leakage impedance is
A
$$0.20$$
B
$$0.10$$
C
$$0.25$$
D
$$0.025$$
2
GATE EE 2006
MCQ (Single Correct Answer)
+2
-0.6
A $$300$$ $$kVA$$ transformer has $$95\% $$ efficiency at full load $$0.8$$ $$pf$$ lagging and $$96\% $$ efficiency at half load, unity $$pf.$$

The iron loss $$\left( {{P_i}} \right)$$ in $$kW,$$ under full load operation are

A
$${P_c} = 4.12,\,\,{P_i} = 8.51$$
B
$${P_c} = 6.59,\,\,{P_i} = 9.21$$
C
$${P_c} = 8.51,\,\,{P_i} = 4.12$$
D
$${P_c} = 12.72,\,\,{P_i} = 3.07$$
3
GATE EE 2006
MCQ (Single Correct Answer)
+1
-0.3
In transformers, which of the following statements is valid?
A
In an open circuit test, copper losses are obtained while in short circuit test, core losses are obtained.
B
In an open circuit test, current is drawn at high power factor.
C
In a short circuit test, current is drawn at zero power factor
D
In an open circuit test, current is drawn at low power factor.
4
GATE EE 2006
MCQ (Single Correct Answer)
+2
-0.6
A $$220V$$ $$DC$$ machine supplies $$20$$ $$A$$ at $$200V$$ as a generator. The armature resistance is $$0.2$$ ohm. If the machine is now operated as a motor at same terminal voltage and current but with the flux increased by $$10\% ,$$ the ratio of motor speed to generator speed is
A
$$0.87$$
B
$$0.95$$
C
$$0.96$$
D
$$1.06$$