1
GATE EE 2001
MCQ (Single Correct Answer)
+2
-0.6
A $$50$$ Hz alternator is rated $$500$$ $$MVA,$$ $$20$$ $$kV,$$ with $${X_d} = 1.0$$ per unit and $$X'{'_d} = 0.2$$ per unit. It supplies a purely resistive load of $$400$$ $$MW$$ at $$20$$ $$kV.$$ The load is connected directly across the generator terminals when a symmetrical fault occurs at the load terminals. The initial rms current in the generator in per units is
A
$$7.22$$
B
$$6.4$$
C
$$3.22$$
D
$$2.2$$
2
GATE EE 2001
Subjective
+5
-0
A synchronous generator is connected to an infinite bus through a lossless double circuit transmission line. The generator is delivering 1.0 per unit power at a load angle of $${30^0}$$ when a sudden fault reduces the peak power that can be transmitted to 0.5 per unit. After clearance of fault, the peak power that can be transmitted becomes 1.5 per unit. Find the critical clearing angle.
3
GATE EE 2001
Subjective
+5
-0
A 132 kV transmission line AB is connected to a cable BC. The characteristic impedances of the overhead line and the cable are 400$$\Omega $$ and 80$$\Omega $$ respectively. Assume that these are purely resistive. A 250 kV switching surge travels from A to B.

(a) Calculate the value of this voltage surge when it first reaches C.

(b) Calculate the value of the reflected component of this surge when the first reflection reaches A.

(c) Calculate the surge current in the cable BC.

4
GATE EE 2001
MCQ (Single Correct Answer)
+1
-0.3
A lossless radial transmission line with surge impedance loading
A
Takes negative VAR at sending end and zero VAR at receiving end.
B
Takes positive VAR at sending end and zero VAR at receiving end.
C
Has flat voltage profile and unity power factor at all points along it.
D
Has sending end voltage higher than receiving end voltage and unity power factor at sending end.