1
GATE EE 1998
MCQ (Single Correct Answer)
+2
-0.6
A shunt reactor of $$100$$ MVAR is operated at $$98$$% of its rated voltage and $$96$$% of its rated frequency. The reactive power absorbed by the reactor is;
A
$$98$$ MVAR
B
$$104.02$$ MVAR
C
$$96.04$$ MVAR
D
$$100.04$$ MVAR
2
GATE EE 1998
MCQ (Single Correct Answer)
+2
-0.6
A power station consists of two synchronous generators A and B of ratings 250 MVA and 500 MVA with inertia constant 1.6 p.u. and 1.0 p.u., respectively on their own base MVA ratings. The equivalent p.u. inertia constant for the system on 100 MVA common base is
A
2.6
B
0.615
C
1.625
D
9.0
3
GATE EE 1998
MCQ (Single Correct Answer)
+1
-0.3
Series capacitive compensation in $$EHV$$ transmission lines is used to
A
Reduce the line loading
B
Improve the stability of the system
C
Reduce the voltage profile
D
Improve the protection of the line.
4
GATE EE 1998
MCQ (Single Correct Answer)
+2
-0.6
For the network shown in figure the zero sequence reactances in p.u. are indicated. The zero sequence driving point reactance of the node 3 is GATE EE 1998 Power System Analysis - Symmetrical Components and Symmetrical and Unsymmetrical Faults Question 37 English
A
0.12
B
0.30
C
0.10
D
0.20