1
GATE EE 2014 Set 3
MCQ (Single Correct Answer)
+2
-0.6
An open circuit test is performed on 50 Hz transformer, using variable frequency source and keeping V/f ratio constant, to separate its eddy current and hysteresis losses. The variation of core loss/frequency as function of frequency is shown in the figure GATE EE 2014 Set 3 Electrical Machines - Transformers Question 67 English The hysteresis and eddy current losses of the transformer at 25 Hz respectively are
A
250 W and 2.5 W
B
250 W and 62.5 W
C
312.5 W and 62.5 W
D
312.5 W and 250 W
2
GATE EE 2014 Set 3
Numerical
+1
-0
The no-load speed of a 230 V separately excited dc motor is 1400 rpm. The armature resistance drop and the brush drop are neglected. The field current is kept constant at rated value. The torque of the motor in Nm for an armature current of 8 A is ____________.
Your input ____
3
GATE EE 2014 Set 3
Numerical
+2
-0
The load shown in the figure absorbs 4 kW at a power factor of 0.89 lagging. GATE EE 2014 Set 3 Electrical Machines - Transformers Question 68 English Assuming the transformer to be ideal, the value of the reactance X to improve the input power factor to unity is ___________.
Your input ____
4
GATE EE 2014 Set 3
MCQ (Single Correct Answer)
+2
-0.6
The mean thickness and variance of silicon steel laminations are 0.2 mm and 0.02 respectively. The varnish insulation is applied on both the sides of the laminations. The mean thickness of one side insulation and its variance are 0.1 mm and 0.01 respectively. If the transformer core is made using 100 such varnish coated laminations, the mean thickness and variance of the core respectively are
A
30 mm and 0.22
B
30 mm and 2.44
C
40 mm and 2.44
D
40 mm and 0.24