1
GATE EE 2010
MCQ (Single Correct Answer)
+2
-0.6
Consider a three-phase, $$50Hz,$$ $$11$$ $$kV$$ distribution system. Each of the conductors is suspended by an insulator string having two identical porcelain insulators. The self capacitance of the insulator is $$5$$ times the shunt capacitance between the link an the ground, as shown in the figure. The voltage across the two insulators are GATE EE 2010 Power System Analysis - Parameters and Performance of Transmission Lines Question 31 English
A
$${e_1} = 3.74\,kV,\,{e_2} = 2.61\,kV$$
B
$${e_1} = 3.46\,kV,\,{e_2} = 2.89\,kV$$
C
$${e_1} = 6.0\,kV,\,{e_2} = 4.23\,kV$$
D
$${e_1} = 5.5\,kV,\,{e_2} = 5.5\,kV$$
2
GATE EE 2010
MCQ (Single Correct Answer)
+2
-0.6
The zero-sequence circuit of the three phase transformer shown in the figure is GATE EE 2010 Power System Analysis - Symmetrical Components and Symmetrical and Unsymmetrical Faults Question 15 English
A
GATE EE 2010 Power System Analysis - Symmetrical Components and Symmetrical and Unsymmetrical Faults Question 15 English Option 1
B
GATE EE 2010 Power System Analysis - Symmetrical Components and Symmetrical and Unsymmetrical Faults Question 15 English Option 2
C
GATE EE 2010 Power System Analysis - Symmetrical Components and Symmetrical and Unsymmetrical Faults Question 15 English Option 3
D
GATE EE 2010 Power System Analysis - Symmetrical Components and Symmetrical and Unsymmetrical Faults Question 15 English Option 4
3
GATE EE 2010
MCQ (Single Correct Answer)
+2
-0.6
A three-phase, $$33$$ kV oil circuit breaker is rated $$1200$$ A, $$2000$$ MVA, $$3$$s. The symmetrical breaking current is
A
$$1200$$ A
B
$$3600$$ A
C
$$35$$ kA
D
$$104.8$$ kA
4
GATE EE 2010
MCQ (Single Correct Answer)
+2
-0.6
Consider a stator winding of an alternator with an internal high resistance ground fault. The currents under the fault condition are as shown in the figure. The winding is protected using a differential current scheme with current transformers of ratio $$400/5$$ $$A$$ as shown. The current through the operating coil is GATE EE 2010 Power System Analysis - Switch Gear and Protection Question 8 English
A
$$0.1875$$ $$A$$
B
$$0.2$$ $$A$$
C
$$0.375$$ $$A$$
D
$$60$$ $$kA$$