1
GATE EE 2004
MCQ (Single Correct Answer)
+2
-0.6
A $$3$$-phase generator rated at $$110$$ MVA, $$11$$ kV is connected through circuit breakers to a transformer. The generator is having direct axis sub-transient reactance $$X'{'_d} = 19\% ,\,\,$$ transient reactance $$X{'_d} = 26\% \,\,$$ and synchronous reactance $$=130$$%. The generator is operating at no load and rated voltage when a three phase short circuit fault occurs between the breakers and the transformer. The magnitude of initial symmetrical rims current in the breakers will be
A
$$4.44$$ kA
B
$$22.20$$ kA
C
$$30.39$$ kA
D
$$38.45$$ kA
2
GATE EE 2004
MCQ (Single Correct Answer)
+1
-0.3
The transmission line distance protection relay having the property of being inherently directional is
A
impedance relay
B
MHO relay
C
OHM relay
D
reactance relay
3
GATE EE 2004
MCQ (Single Correct Answer)
+1
-0.3
In thermal power plants, the pressure in the working fluid cycle is developed by
A
Condenser
B
Super heater
C
Feed water pump
D
Turbine
4
GATE EE 2004
MCQ (Single Correct Answer)
+1
-0.3
For harnessing low variable water heads, the suitable hydraulic turbine with high percentage of reaction and runner adjustable vanes is
A
Kaplan
B
Francis
C
Pelton
D
Impeller