Total instantaneous power supplied by a $$3$$-phase ac supply to a balanced $$R$$-$$L$$ load is
A
Zero
B
Constant
C
Pulsating with zero average
D
Pulsating with non-zero average
2
GATE EE 2004
MCQ (Single Correct Answer)
+2
-0.6
A $$3$$-phase generator rated at $$110$$ MVA, $$11$$ kV is connected through circuit breakers to a transformer. The generator is having direct axis sub-transient reactance $$X'{'_d} = 19\% ,\,\,$$ transient reactance $$X{'_d} = 26\% \,\,$$ and synchronous reactance $$=130$$%. The generator is operating at no load and rated voltage when a three phase short circuit fault occurs between the breakers and the transformer. The magnitude of initial symmetrical rims current in the breakers will be
A
$$4.44$$ kA
B
$$22.20$$ kA
C
$$30.39$$ kA
D
$$38.45$$ kA
3
GATE EE 2004
MCQ (Single Correct Answer)
+2
-0.6
A new generator having $${E_g} = 1.4\,\angle {30^ \circ }\,$$ pu [ equivalent to ($$1.212 +j$$ $$0.70$$)pu ] and synchronous reactance $$'{X_s}'$$ of $$1.0$$ pu on the system base, is to be connected to a bus having voltage $${V_t}$$ in the existing power system. This existing power system can be represented by Thevenin's voltage $${E_{th}} = 0.9\angle {0^ \circ }\,\,$$ pu in series with Tjhevenin's impedance $${Z_{th}} = 0.25\angle {90^ \circ }\,\,$$ pu. The magnitude of the voltage $${V_t},$$ of the system in pu will be
A
$$0.990$$
B
$$0.973$$
C
$$0.963$$
D
$$0.900$$
4
GATE EE 2004
MCQ (Single Correct Answer)
+1
-0.3
For harnessing low variable water heads, the suitable hydraulic turbine with high percentage of reaction and runner adjustable vanes is
A
Kaplan
B
Francis
C
Pelton
D
Impeller