1
GATE EE 2014 Set 1
Numerical
+2
-0
The over current relays for the line protection and loads connected at the buses are shown in the figure. GATE EE 2014 Set 1 Power System Analysis - Switch Gear and Protection Question 7 English

The relays are IDMT is natural having the characteristic
$${t_{op}} = {{0.14\, \times \,time\,\,multiplier\,\,setting} \over {{{(plug\,\,setting\,\,multiplier)}^{0.02}} - 1}}$$
The maximum and minimum fault current at bus $$B$$ are $$2000A$$ and $$500$$ $$A$$ respectively. Assuming the time multiplier setting and plug setting for relay $${R_B}$$ to be $$0.1$$ and $$5$$ $$A$$ respectively, the operating time of $${R_B}$$ (in seconds) is __________.

Your input ____
2
GATE EE 2014 Set 1
MCQ (Single Correct Answer)
+1
-0.3
A 2-bus system and corresponding zero sequence network are shown in the figure. GATE EE 2014 Set 1 Power System Analysis - Symmetrical Components and Symmetrical and Unsymmetrical Faults Question 36 English

The transformers T1 and T2 are connected as

A
GATE EE 2014 Set 1 Power System Analysis - Symmetrical Components and Symmetrical and Unsymmetrical Faults Question 36 English Option 1
B
GATE EE 2014 Set 1 Power System Analysis - Symmetrical Components and Symmetrical and Unsymmetrical Faults Question 36 English Option 2
C
GATE EE 2014 Set 1 Power System Analysis - Symmetrical Components and Symmetrical and Unsymmetrical Faults Question 36 English Option 3
D
GATE EE 2014 Set 1 Power System Analysis - Symmetrical Components and Symmetrical and Unsymmetrical Faults Question 36 English Option 4
3
GATE EE 2014 Set 1
MCQ (Single Correct Answer)
+1
-0.3
The undesirable property of an electrical insulating material is
A
high dielectric strength
B
high relative permittivity
C
high thermal conductivity
D
high insulation resistivity
4
GATE EE 2014 Set 1
MCQ (Single Correct Answer)
+2
-0.6
A distribution feeder of $$1$$ $$km$$ length having resistance, but negligible reactance, is fed from both the ends by $$400$$ $$V,$$ $$50$$ $$Hz$$ balanced sources. Both voltage sources $${S_1}$$ and $${S_2}$$ are in phase. The feeder supplies concentrated loads of unity power factor as shown in the figure. GATE EE 2014 Set 1 Power System Analysis - Parameters and Performance of Transmission Lines Question 27 English

The contributions of $${S_1}$$ and $${S_2}$$ in $$100$$ $$A$$ current supplied at location $$P$$ respectively, are

A
$$75$$ $$A$$ and $$25A$$
B
$$50A$$ and $$50A$$
C
$$25A$$ to $$75A$$
D
$$0A$$ and $$100A$$