GATE EE 1995
Numerical
+1
-0
The percentage impedance of a 100 kVA, 11 kV/400V, delta/wye, 50 Hz transformer is 4.5%. For the circulation of half the full load current during short circuit test, with low voltage terminals shorted, the applied voltage on the high voltage side will be __________.
Your input ____
2
GATE EE 1995
MCQ (Single Correct Answer)
+1
-0.3
Supply to one terminal of a $$\triangle$$ - Y connected three-phase core type transformer which is on no-load, fails. Assuming magnetic circuit symmetry, voltages on the secondary side will be:
A
230, 230, 115
B
230, 115, 115
C
345, 115, 115
D
345, 0, 345
3
GATE EE 1995
MCQ (Single Correct Answer)
+1
-0.3
An induction motor is fed from a balanced three phase supply at rated voltage and frequency through a bank of three single phase transformers connected in delta-delta. One unit of the bank develops fault and is removed. Then
A
single phasing will occur and the machine fails to start
B
single phasing will not occur but the motor terminal voltages will become unbalanced and the machine can be loaded to the extent of 57.7% of its rating.
C
the machine can be loaded to the extent of 57.7% of its rating with balanced supply at its terminals.
D
the machine can be loaded to the extent of $$66\frac23\%$$ with balanced supply at its terminals.
4
GATE EE 1995
MCQ (Single Correct Answer)
+1
-0.3
A synchronous motor on load draws a current at a leading power factor angle $$\phi$$. If the internal power factor angle – which is the phase angle between the excitation e.m.f. and the current in the time phasor diagram is $$\psi$$, then the air gap excitation m.m.f lags the armature m.m.f by
A
$$\psi$$
B
$$\frac{\mathrm\pi}2+\psi$$
C
$$\frac{\mathrm\pi}2-\psi$$
D
$$\psi+\phi$$