1
GATE EE 2016 Set 1
Numerical
+2
-0
A three-phase cable is supplying $$800$$ kW and $$600$$ kVAr to an inductive load. It is intended to supply an additional resistive load of $$100$$ kW through the same cable without increasing the heat dissipation in the cable, by providing a three-phase bank of capacitors connected in star across the load. Given the line voltage is $$3.3$$ kV, $$50$$ Hz, the capacitance per phase of the bank expressed in microfarads, is ________.
Your input ____
2
GATE EE 2016 Set 1
Numerical
+2
-0
A 30 MVA, 3-phase, 50Hz, 13.8 kV, star-connected synchronous generator has positive, negative and zero sequence reactances, 15%, 15% and 5% respectively. A reactance (Xn) is connected between the neutral of the generator and ground. A double line to ground fault takes place involving phases ‘b’ and ‘c’, with a fault impedance of j0.1 p.u. The value of Xn (in p.u.) that will limit the positive sequence generator current to 4270 A is __________.
Your input ____
3
GATE EE 2016 Set 1
Numerical
+1
-0
The magnitude of three-phase fault currents at buses A and B of a power system are 10 pu and 8 pu, respectively. Neglect all resistances in the system and consider the pre-fault system to be unloaded. The pre-fault voltage at all buses in the system is 1.0 pu. The voltage magnitude at bus B during a three-phase fault at bus A is 0.8 pu. The voltage magnitude at bus A during a three-phase fault at bus B in pu, is __________.
Your input ____
4
GATE EE 2016 Set 1
MCQ (Single Correct Answer)
+1
-0.3
In a 100 bus power system, there are 10 generators. In a particular iteration of Newton Raphson load flow technique (in polar coordinates), two of the PV buses are converted to PQ type. In this iteration.
A
the number of unknown voltage angles increases by two and the number of unknown voltage magnitudes increases by two.
B
the number of unknown voltage angles remains unchanged and the number of unknown voltage magnitudes increases by two.
C
the number of unknown voltage angles increases by two and the number of unknown voltage magnitudes decreases by two.
D
the number of unknown voltage angles remains unchanged and the number of unknown voltage magnitudes decreases by two