1
GATE EE 2016 Set 1
Numerical
+2
-0
The switches $$T1$$ and $$T2$$ in Figure are switched in a complementary fashion with sinusoidal pulse width modulation technique. The modulating voltage $${v_m}\left( t \right) = 0.8\sin \left( {200\pi t} \right)\,\,V$$ and the triangular carrier $$\left( {{V_c}} \right),$$ voltage $$\left( {{V_c}} \right)$$ are as shown in figure $$(b).$$ The carrier frequency is $$5$$ $$kHz.$$ The peak value of the $$100$$ $$Hz$$ component of the load current $$\left( {{i_L}} \right)$$ in Ampere, is ______. GATE EE 2016 Set 1 Power Electronics - Inverters Question 7 English 1 GATE EE 2016 Set 1 Power Electronics - Inverters Question 7 English 2
Your input ____
2
GATE EE 2016 Set 1
Numerical
+2
-0
A single-phase transmission line has two conductors each of 10 mm radius. These are fixed at a center-to-center distance of 1 m in a horizontal plane. This is now converted to a three-phase transmission line by introducing a third conductor of the same radius. This conductor is fixed at an equal distance D from the two single-phase conductors. The three-phase line is fully transposed. The positive sequence inductance per phase of the three phase system is to be 5% more than that of the inductance per conductor of the single phase system. The distance D, in meters, is ________.
Your input ____
3
GATE EE 2016 Set 1
Numerical
+2
-0
A three-phase cable is supplying $$800$$ kW and $$600$$ kVAr to an inductive load. It is intended to supply an additional resistive load of $$100$$ kW through the same cable without increasing the heat dissipation in the cable, by providing a three-phase bank of capacitors connected in star across the load. Given the line voltage is $$3.3$$ kV, $$50$$ Hz, the capacitance per phase of the bank expressed in microfarads, is ________.
Your input ____
4
GATE EE 2016 Set 1
Numerical
+2
-0
A 30 MVA, 3-phase, 50Hz, 13.8 kV, star-connected synchronous generator has positive, negative and zero sequence reactances, 15%, 15% and 5% respectively. A reactance (Xn) is connected between the neutral of the generator and ground. A double line to ground fault takes place involving phases ‘b’ and ‘c’, with a fault impedance of j0.1 p.u. The value of Xn (in p.u.) that will limit the positive sequence generator current to 4270 A is __________.
Your input ____