1
GATE EE 2015 Set 1
Numerical
+2
-0
A 50 Hz generating unit has H-constant of 2 MJ/MVA. The machine is initially operating in steady state at synchronous speed, and producing 1 pu of real power. The initial value of the rotor angle $$\delta $$ is $${5^ \circ }$$, when a bolted three phase to ground short circuit fault occurs at the terminal of the generator. Assuming the input mechanical power to remain at 1 pu, the value of $$\delta $$ in degrees, 0.02 second after the fault is _____________
Your input ____
2
GATE EE 2015 Set 1
MCQ (Single Correct Answer)
+1
-0.3
Consider a $$HVDC$$ link which uses thyristor based line commutated converters as shown in the figure. For a power flow of $$750$$ $$MW$$ from System $$1$$ to System $$2,$$ the voltages at the two ends, and the current, are given by: $${V_1} = 500\,kV,\,\,{V_2} = 485\,kV\,\,$$ and $$\,{\rm I} = 1.5\,kA.\,\,$$ If the direction of power flow is to be reversed (that is, from System $$2$$ to System $$1$$) without changing the electrical connections, then which one of the following combinations is feasible? GATE EE 2015 Set 1 Power System Analysis - High Voltage Dc Transmission Question 1 English
A
$${V_1} = - 500\,kV,\,\,\,{V_2} = - 485\,kV$$ and $$\,\,\,{\rm I} = 1.5\,kA$$
B
$${V_1} = - 485\,kV,\,\,\,{V_2} = - 500\,kV$$ and $$\,\,\,{\rm I} = 1.5\,kA$$
C
$${V_1} = 500\,kV,\,\,\,{V_2} = 485\,kV$$ and $$\,\,\,{\rm I} = -1.5\,kA$$
D
$${V_1} = - 500\,kV,\,\,\,{V_2} = - 485\,kV$$ and $$\,\,\,{\rm I} = -1.5\,kA$$
3
GATE EE 2015 Set 1
MCQ (Single Correct Answer)
+2
-0.6
Determine the correctness or otherwise of the following Assertion (a) and the Reason (R).
Assertion (A): Fast decoupled load flow method gives approximate load flow solution because it uses several assumptions.
Reason (R): Accuracy depends on the power mismatch vector tolerance.
A
Both (A) and (R) are true and (R) is the correct reason for (A)
B
Both (A) and (R) are true but (R) is not the correct reason for (A)
C
Both (A) and (R) are false
D
(A) is false and (R) is true
4
GATE EE 2015 Set 1
MCQ (Single Correct Answer)
+2
-0.6
A sustained three phase fault occurs in the power system shown in the figure. The current and voltage phasors during the fault (on a common reference), after the natural transients have died down, are also shown. Where is the fault located? GATE EE 2015 Set 1 Power System Analysis - Symmetrical Components and Symmetrical and Unsymmetrical Faults Question 17 English
A
Location $$P$$
B
Location $$Q$$
C
Location $$R$$
D
Location $$S$$