1
GATE EE 2015 Set 1
Numerical
+2
-0
A 50 Hz generating unit has H-constant of 2 MJ/MVA. The machine is initially operating in steady state at synchronous speed, and producing 1 pu of real power. The initial value of the rotor angle $$\delta $$ is $${5^ \circ }$$, when a bolted three phase to ground short circuit fault occurs at the terminal of the generator. Assuming the input mechanical power to remain at 1 pu, the value of $$\delta $$ in degrees, 0.02 second after the fault is _____________
Your input ____
2
GATE EE 2015 Set 1
MCQ (Single Correct Answer)
+2
-0.6
A sustained three phase fault occurs in the power system shown in the figure. The current and voltage phasors during the fault (on a common reference), after the natural transients have died down, are also shown. Where is the fault located? GATE EE 2015 Set 1 Power System Analysis - Symmetrical Components and Symmetrical and Unsymmetrical Faults Question 12 English
A
Location $$P$$
B
Location $$Q$$
C
Location $$R$$
D
Location $$S$$
3
GATE EE 2015 Set 1
Numerical
+2
-0
Consider the economic dispatch problem for a power plant having two generating units. The fuel costs in $$Rs/MWh$$ along with the generation limits for the two units are given below:
$$\eqalign{ & {C_1}\left( {{P_1}} \right) = 0.01\,P_1^2 + 30{P_1} + 10; \cr & \,\,\,\,\,\,\,\,\,\,\,\,\,\,\,\,\,\,\,\,\,\,100\,MW \le {P_1} \le 150\,MW \cr} $$
$$\eqalign{ & {C_2}\left( {{P_2}} \right) = 0.05\,P_2^2 + 10{P_2} + 10; \cr & \,\,\,\,\,\,\,\,\,\,\,\,\,\,\,\,\,\,\,\,\,\,100\,MW \le {P_2} \le 180\,MW \cr} $$

The incremental cost (in $$Rs/MWh$$) of the power plant when it supplies $$200$$ $$MW$$ is __________.

Your input ____
4
GATE EE 2015 Set 1
MCQ (Single Correct Answer)
+1
-0.3
Base load power plants are
$$P.$$ wind farms
$$Q.$$ run-of-river plants
$$R.$$ nuclear power plants
$$S.$$ diesel power plants
A
P, Q and S only
B
P, R and S only
C
P, Q and R only
D
Q and R only
EXAM MAP
Medical
NEET
Graduate Aptitude Test in Engineering
GATE CSEGATE ECEGATE EEGATE MEGATE CEGATE PIGATE IN
CBSE
Class 12