1
GATE EE 1996
MCQ (Single Correct Answer)
+1
-0.3
If the fault current is $$2000$$ A, the relay setting is $$50$$% and CT ratio is $$400:5,$$ the plug setting multiplier will be
A
$$25$$
B
$$15$$
C
$$50$$
D
$$10$$
2
GATE EE 1996
MCQ (Single Correct Answer)
+1
-0.3
For a $$500$$ Hz frequency excitation, a $$50$$ km short power line will be modeled as
A
Short line
B
Medium line
C
Long line
D
Data insufficient for decision.
3
GATE EE 1996
MCQ (Single Correct Answer)
+1
-0.3
For an unbalanced fault, with paths for zero sequence currents, at the point of fault
A
The negative and zero sequence voltages are minimum.
B
The negative and zero sequence voltages are maximum.
C
The negative sequence voltage is minimum and zero sequence voltage is maximum.
D
The negative sequence voltage is maximum and zero sequence voltage is minimum.
4
GATE EE 1996
MCQ (Single Correct Answer)
+1
-0.3
During a disturbance on synchronous machine, the rotor swings from A to B before finally settling down to a steady state at a point C on the power angle curve. The speed of the machine during oscillation is synchronous at point(s)
A
A and B
B
A and C
C
B and C
D
Only at C